| Voltage |
Range: 20 Volts to 500 kiloVolts
Accuracy: 0.2%
Resolution: 0.1 Volts |
| Current |
Range: 5 mA to 50,000 Amps
Accuracy: 0.2%
Resolution: 0.001 Amps |
| Power |
Range: -9999 MW to 9999 MW
Accuracy: 0.2%
Resolution: 1 Watt |
| Reactive Power |
Range: -9999 MVar to 9999 MVar
Accuracy: 0.5%
Resolution: 1 Var |
| Apparent Power |
Range: -9999 MVA to 9999 MVA
Accuracy: 0.2%
Resolution: 1 VA |
| Power Demand |
Range: -9999 MW to 9999 MW
Accuracy: 0.2%
Resolution: 1 W |
| Reactive Power Demand |
Range: -9999MVar to 9999MVar
Accuracy: 0.2%
Resolution: 1 Var |
| Apparent Power Demand |
Range: -9999 MVA to 9999 MVA
Accuracy: 0.2%
Resolution: 1 VA |
| Power Factor |
Range: -1.000 to 1.000
Accuracy: 0.2%
Resolution: 0.001 |
| Frequency |
Range: 45.00 Hz to 65.00 Hz
Accuracy: 0.2%
Resolution: 0.01 Hz |
| Energy (Primary) |
Range: 0 to 99999999.9 kWh
Accuracy: 0.2%
Resolution: 0.1 kWh |
| Energy (Secondary) |
Range: 0 to 999999.999 kWh
Accuracy: 0.2%
Resolution: 0.001 kWh |
| Reactive Energy (Primary) |
Range: 0 to 99999999.9 kVarh
Accuracy: 0.2%
Resolution: 0.1 kvarh |
| Reactive Energy (Secondary) |
Range: 0 to 999999.999 kVarh
Accuracy: 0.2%
Resolution: 0.001 kvarh |
| Apparent Energy (Primary) |
Range: 0 to 99999999.9 kVAh
Accuracy: 0.2%
Resolution: 0.1 kVAh |
| Apparent Energy (Secondary) |
Range: 0 to 999999.999 kVAh
Accuracy: 0.2%
Resolution: 0.001 kVAh |
| Harmonics |
Range: 0 to 100%
Accuracy: 2.0%
Resolution: 0.1% |
| Phase Angle |
Range: 0° to 359.9°
Accuracy: 2.0%
Resolution: 0.1° |
| Unbalance Factor |
Range: 0 to 100%
Accuracy: 2.0%
Resolution: 0.1% |
| Running Time |
Range: 0 to 9999999.99h
Resolution: 0.01h |
Current Inputs (Each Channel) |
Nominal Current: 5A ac
Metering Range: 0 to 10 A ac
Withstand: 20 Arms (Continuous); 100 Arms (1 Sec., non-recurring)
Burden: 0.05VA (typical) @ 5Arms
Pickup Current: 0.1% of Nominal
Accuracy: 0.2% Full Scale |
Voltage Inputs
(Each Channel) |
Nominal Full Scale: 400 Vac L-N, 690 Vac L-L
Withstand: 1500Vac (Continuous); 3250 Vac, 50/60 Hz (1 min.)
Input Impedance: 2Mohm per phase
Metering Frequency: 45 Hz to 65 Hz
Pickup Voltage: 30Vac
Accuracy: 0.2% Full Scale |
| Energy Accuracy |
Active: Class 0.2S (According to IEC 62053-22)
Reactive: Class 2 (According to IEC 62053-23) |
| Harmonic Resolution |
Metered Value: 63rd Harmonic |
| AC/DC Control Power |
Operating Range: 100-415 Vac, 50/60 Hz; 100-300 Vdc
Burden: 5W
Frequency: 50/60 Hz
Withstand: 3250 Vac, 50/60 Hz for 1 Minute
Installation Category III (Distribution) |
| Low Voltage DC Control Power (Optional) |
Operating Range: 20 to 60 Vdc
Burden: 5W |
| Digital Input (DI) |
Input Voltage Range: 20 to 220 Vac/dc
Input Current (Max): 2mA
Start Voltage: 15 Volts
Stop Voltage: 5 Volts
Pulse Frequency (Max): 100 Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
SOE Resolution: 2 ms |
Digital Output (DO) (Photo-MOS) |
Voltage Range: 0 to 250 Vac/dc
Load Current: 100mA (Max)
Output Frequency: 25 Hz, 50% Duty Ratio (20ms ON and 20ms OFF)
Isolation Voltage: 2500 Vac |
| Relay Output (RO) |
Switching Voltage: 250 Vac, 30Vdc (Max)
Load Current: 5A (R), 2A (L)
Set Time: 10ms (Max)
Contact Resistance: 30mΩ (Max)
Isolation Voltage: 3000 Vac
Mechanical Life: 1.5 x 107 |
| Analog Output (AO) |
Output Range: 0 to 5 Volts; 1 to 5 Volts; 0 to 20mA; 4 to 20mA (Optional)
Accuracy: 0.5%
Temperature Drift: 50ppm/°C Typical
Isolation Voltage: 500 Vdc
Open Circuit Voltage: 15 Volts |
| Analog Input (AI) |
Input Range: 0 to 5 Volts; 1 to 5 Volts; 0 to 20mA; 4 to 20mA (Optional)
Accuracy: 0.2%
Temperature Drift: 50ppm/°C Typical
Isolation Voltage: 500 Vdc |
Power Supply (Digital Input) |
Output Voltage: 24 Volts DC
Output Current: 42 mA
Load: 21 Digital Inputs (Max) |
| Communications |
RS-485 (Standard); Ethernet, PROFI-BUS (Optional) |
| RS-485 Communications |
Protocol: MODBUS RTU (Industry Standard)
Type: 2 Wire Connection
Baud Rate: Up to 38,400 |
Ethernet Communications (Optional) |
10M/100M BaseT
MODBUS RTU Protocol
Data Browsing Through HTTP
Sending E-mail Automatically |
PROFI-BUS Communications (Optional) |
PROFIBUS RTU Protocol
Works as PROFIBUS Slave, Baud Rate Adaptive, Up to 12M
Typical Input Bytes: 32 Typical Output Bytes: 32 PROFIBUS Standard According to EN 50170 Vol. 2 |
| Display |
LCD Screen Display with White Back Light Wide Environmental Temperature Endurance Displays Load Percentage, 4 Quandrants Power and Load Nature |
| Alarms |
Up to 16 Parameters Set with Time Interval Events Recorded with Time Stamps and Triggers Alarm DO Output (44 Different Parameters Available) |
| Operating Range |
Temperature: -25°C to 70°C
Humidity: 5% to 95% Non-Condensing
Pollution Degree: 2 |
| Storage Range |
Temperature: -40°C to 85°C
Humidity: 5% to 95% Non-Condensing |
| Standards Compliance |
Measurement: IEC 62053-22; ANSI C12.20
Environmental: IEC 60068-2
Safety: IEC 61010-4; UL 61010-1
EMC: IEC 61000-4/-2-3-4-5-6-8-11; CISPR 22
Outlines: DIN 43700; ANSI C39.1 |
| Dimensions |
9.6cm x 9.6cm x 5.07cm (3.8" x 3.8" x 2.0") |