Acuvim-L Series Multifunction Power Meter

AccuEnergy Meter for Controlling and Monitoring Power and Energy Distribution Systems
SKU
ACUVIM-L
$280.00
  • Power Meter Measures 3-Phase Voltage, Current, Power (Reactive, Apparent, Active), Energy, Power Factor, Run Time, THD and Individual Harmonics 2nd to 63rd (EL Model), or 2nd to 31st (CL Model)
  • (2) Different Alarm Parameters for High and Low Alarm Alerts
  • Compatible with Single or Three-Phase Electrical Systems
  • (2) Pulse Digital Outputs for kWh and kvarh with Configurable Rate and Width
  • ±0.2% Accuracy with ANSI C12.20 Standard for Revenue Grade Meters
  • Can accept up to (1) I/O Modules (AXM-IO1, AXM-IO2 or AXM-IO3) for the EL Meter Series
  • If a Communications Module (AXM-PROFI, AXM-WEB-PUSH or AXM-WEB2) is Attached, only (2) I/O Modules can be Added

AcuView Software for Remote Meter Access and Control, Real-Time Monitoring and Local PC Logging Available for Download

Due to Increased Freight Costs, All AccuEnergy Orders Must Have a Minimum Order Value of $100

Special order - please allow 2-4 weeks for this item to ship.

Overview of the Acuvim-L Multifunction Power Meter

The Acuvim-L Series are three phase multifunction power meters from Accuenergy, one of the leading power meter manufacturers. It is a perfect choice for monitoring and controlling power distribution systems, medium to low voltage systems, industrial automation, and commercial facility applications. It is available in 2 different models to suite a wide range of applications and each model can be used with a wide selection of current transformers. Some models can be equipped with optional digital/analog I/O or PROFIBUS.

User Manuals and Product Guides
Software Downloads
zip
(Size: 3.3 MB)

Multifunction Power Meter Specifications

Voltage Range: 10 Volts to 1000 kiloVolts
Accuracy: 0.10%
Resolution: 0.1 Volts
Current Range: 5mA to 50,000 Amps
Accuracy: 0.10%
Resolution: 0.1 Amps
Current Demand Range: 5mA to 50,000 Amps
Accuracy: 0.10%
Resolution: 0.1 Amps
Power Range: -9999 MW to 9999 MW
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 Watt
Reactive Power Range: -9999 MVar to 9999 MVar
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 Var
Apparent Power Range: 0 to 9999 MVA
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 VA
Power Demand Range: -9999 MW to 9999 MW
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 W
Reactive Power Demand Range: -9999MVar to 9999MVar
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 Var
Apparent Power Demand Range: 0 to 9999 MVA
Accuracy: 0.20% EL and 0.50% CL
Resolution: 1 VA
Power Factor Range: -1.0 to 1.0
Accuracy: 0.10%
Resolution: 0.001
Frequency Range: 45.00 Hz to 65.00 Hz
Accuracy: 0.00%
Resolution: 0.001 Hz
Energy Range: 0 to 99,999,999.9 kWh
Accuracy: 0.20% EL and 0.50% CL
Resolution: 0.1 kWh
Reactive Energy Range: 0 to 99,999,999.9 kVarh
Accuracy: 0.20% EL and 0.50% CL
Resolution: 0.1 kvarh
Apparent Energy Range: 0 to 99,999,999.9 kVAh
Accuracy: 0.20% EL and 0.50% CL
Resolution: 0.1 VAh
Harmonics Accuracy: 1.00%
Resolution: 0.1%
Running Time Range: 0 to 9,999,999.99 hours
Resolution: 0.1 hours
Current Inputs
(Each Channel)
Nominal Current: 5A, 1A, or 1A(333mV)
Metering Range: 0-10A, 0-2A, or 0-1.2A
Withstand: 20 Arms (Continuous); 100 Arms (1 Sec., non-recurring)
Burden: 0.05VA (typical) @ 5Arms
Pickup Current: 0.1% of Nominal
Accuracy: 0.1% at Reading
Voltage Inputs
(Each Channel)
Nominal Full Scale: 400 VAC L-N, 690 VAC L-L
Withstand: 1500VAC (Continuous); 2500 VAC, 50/60 Hz (1 min.)
Input Impedance: 2Mohm per phase
Metering Frequency: 45 Hz to 65 Hz, 300Hz-500Hz
Pickup Voltage: 10VAC
Accuracy: 0.1% at Reading
Energy Accuracy >Active: Class 0.2S for EL and 0.5S for CL (According to IEC 62053-22) Class 0.2S for EL and 0.5S for CL (According to ANSI C12.20) 
Reactive: Class 0.5 (According to IEC 62053-24)

Harmonic Resolution

2nd to 63rd Harmonic (50Hz or 60Hz type) for EL

2nd to 31st harmonic (50Hz or 60Hz type) for CL

AC/DC Control Power Operating Range: 100-415 VAC; 100-300 VDC 
Burden: 5W
Frequency: 50/60 Hz
Withstand: 3250 Vac, 50/60 Hz for 1 Minute
Installation Category III (Distribution)
Low Voltage DC Control Power (Optional) Operating Range: 20 to 60 VDC 
Burden: 5W
Digital Input (DI) Input Voltage Range: 20 to 160 VAC/DC
Input Current (Max): 2mA
Start Voltage: 15 Volts
Stop Voltage: 5 Volts
Pulse Frequency (Max): 100 Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
SOE Resolution: 2 ms
Digital Output (DO)
(Photo-MOS)
Voltage Range: 0 to 250 VAC/DC
Load Current: 100mA (Max)
Output Frequency: 25 Hz, 50% Duty Ratio (20ms ON and 20ms OFF)
Isolation Voltage: 2500 Vac
Communications Modbus-RTU Protocol; RS-485 (Optional), or BACnet MS/TP, Ethernet (Optional), or Profibus (Optional)
ModBus Communications Protocol: MODBUS RTU (Industry Standard)
Type: 2 Wire Connection, Half-Duplex, Isolated
Baud Rate: 1200 to 38,400
Display LCD Screen Display with White Back Light
Wide Environmental Temperature Endurance
Displays Load Percentage, 4 Quadrants Power and Load Nature
Alarms Up to 2 Parameters Set with Time Interval
Events Recorded with Time Stamps and Triggers Alarm DO Output
(35 Different Parameters Available)
Software Compatibility Windows 11, 10 and 7 (32 and 64-Bit)
Operating Range Temperature: -25°C to 70°C
Humidity: 5% to 95% Non-Condensing
Pollution Degree: 2
Storage Range Temperature: -40°C to 85°C
Humidity: 5% to 95% Non-Condensing
Standards Compliance IEC 61010-1; UL 61010-1; cUL 61010-1
Dimensions 9.6cm x 9.6cm x 5.1cm (3.8" x 3.8" x 2.0")
Customer Questions
Hello! Does the acuvim kl have internal data logging?
No, the L series doesn't have onboard logging capabilities.  For data logging you would need to look at the IIR, IIE, or IIW series of meters. 
Hi, Can "Acuvim-L Series Multifunction Power Meter" log power consumption of a custom microwave oven. We would like to save the power consumption readings in computer.
This product wouldn't be ideal for that application.  Instead we would recommend looking at something that you can plug inline to measure and record power consumption. Here is a link to a product we would recommend - ...
I need a device to monitor with a PC the voltage and current on a line of (nominal) 115 VAC 3-phase 400 Hz 10 Amps. Is this device OK for that?
The Acuvim L series meter will display voltage and current however it is not a data logger so it can't store or retain data for historical review. The only way to record data with it would be to connect it to an external building management system via...
Please, mind that only logged in users can submit questions
Copyright © 2024 MicroDAQ, LLC. All Rights Reserved.