Data Loggers
Other Products
More Information
MicroDAQ.com, Ltd. Toll Free Phone: © 2010 MicroDAQ.com |
PowerPad 3-Phase Power Quality AnalyzerAEMC Logger for Power Diagnostics and Quality on 1, 2 or 3 Phase Networks
|
| Sampling Frequency | 256 Samples/Cycle |
| Data Storage | 2GB SD Card |
| Voltage (TRMS) | Phase-to-Phase: 1000 Volts Phase-to-Neutral: 1000 Volts |
| Current (TRMS) | MN Clamp: 0 to 6A/120A ot 0 to 240A SR Clamp: 0 to 1200 Amps MR Clamp: 0 to 1000Aac, 0 to 1400Adc MiniFlex: 0.1A to 1000A AmpFlex: 0 to 6500 Amps |
| Frequency (Hz) | 40 to 69 Hz |
| Other Measurements | kW, kVAR, kVA, PF, DPF, kWh, kVARh, kVAh, K-Factor, Flicker |
| Harmonics | 1st to 50th, Direction, Sequence |
| Power Source | 9.6 NiMH Rechargeable Battery Pack External AC Supply: 110/230 VAC ±10% (50/60 Hz) |
| Battery Life | Display On: Approximately 8 Hours Display Off: Approximately 35 Hours (Record Mode) |
| Communication Port | Optically Coupled RS-232 |
| Display | 1/4 VGA (320 x 240) Color LCD |
| Dimensions | 9.8" x 7.8" x 2.6" (250mm x 200mm x 67mm) |
| Weight | 4.3 lbs (1.95Kg) |
| Safety Rating | EN 61010-1, 600V Cat. IV**, Pollution Degree 2 |
* Crest Factor at 6500 = 1
** When Used with SR193 or AmpFlex® probes. 600 V Cat III with MN193 or MR193 probes.
All prices are in U.S. Dollars.
No U.S. sales tax