Data Loggers - Your Source for Temperature Data Loggers, Humidity Data Loggers, Pressure Data Loggers,Relative Humidity Data Loggers,CO data loggers,CO2 data loggers,Rainfall Gauges,Soil Moisture Content Measurement and many other data logging,measurement or recording devices

AEMC PowerPad Specifications

Specifications for the AEMC PowerPad Model 3945

ELECTRICAL
Sampling Frequency 256 samples per cycle
Data Storage 4MB partitioned for waveforms, transients, alarms and trend recording
Voltage (TRMS) Phase-to-Phase: 830V Phase-to-Neutral: 480V
Current (TRMS) MN Clamp: 0 to 6A/120A or 0 to 240A
MR Clamp: 0 to 1200AAC, 0 to 1400ADC
SR Clamp: 0 to 1200A
AmpFlex: 0 to 6500A1
MEASUREMENT RANGE RESOLUTION ACCURACY
Single-Phase RMS Voltages 6 to 480V 0.1V ±0.5% ± 2cts
Phase-to-Phase RMS Voltages 10 to 830V 0.1V ±0.5% ± 2cts
Single-Phase Peak Voltages 6 to 680V 1V ±(1% + 5cts)
Phase-to-Phase Peak Voltages 10 to 1360V 1V ±(1% + 5cts)
Frequency (Hz) 40 to 69Hz 0.01Hz ±0.01Hz
DC Voltage Component 6 to 650V 0.1V ±1% ± 2cts
Current Probes
  MN Clamp
  SR Clamp
  AmpFlex Probe

0 to 240A
0 to 1200A
10 to 6500A

0.1A
0.1A; 1A ≥ 1000A
0.1A; 1A ≥ 1000A

±(0.5% + 2cts)
±(0.5% + 2cts)
±(0.5% + 1A)
Active (Real) Power (kW) 0 to 9999kW 4 digits (10,000ct) ±1% ± 1ct @ PF ≥0.8
Reactive Power (kVAR) 0 to 9999kVAR 4 digits (10,000ct) ±1% ± 1ct @ PF ≤0.8
Apparent Power (kVA) 0 to 9999kVA 4 digits (10,000ct) ±1% ± 1ct
Power Factor (PF & DPF) -1.000 to 1.000 0.001 ±(1.5% + 0.01)
Active Energy (kWh) 0 to 9999MWh 4 digits (10,000ct) ±1% ± 1ct @ PF ≥0.8
Reactive Energy (kVARh) 0 to 9999MVARh 4 digits (10,000ct) ±1% ± 1ct @ PF ≤0.8
Apparent Energy (kVAh) 0 to 9999MVAh 4 digits (10,000ct) ±1% ± 1ct
Unbalance (V & A) 0 to 100% 0.1% ±1% ± 1ct
Phase Angle (V-A, A-A, V-V)) -179° to +180° ±2° ± 1ct
Harmonics (1st to 50th)
  F = 40 to 69Hz
  (V ≥ 50V, A > Inom/100)
0 to 999% 0.1% ±1% + 5cts
Total Harmonic Distortion (V & A) 0 to 999% 0.1% ±1% + 5cts
K-factor (Akf) 1 to 99.99 0.01 ±5% ± 1ct
Flicker (PST) 0.00 to 9.99 0.01  
Power Source 9.6V NiMH rechargeable battery pack
AC supply: 110/230VAC ±20% (50/60Hz)
Battery Life 6 hrs with display on; ≤96 hrs with display off (record mode)
ENVIRONMENTAL
Operating Temperature 32° to 122°F (0° to 50°C)
Storage Temperature -4° to +122°F (-20° to +50°C)
MECHANICAL
Display 1/4 VGA (320 x 240) color LCD
Dimensions 9.5 x 7 x 2" (240 x 180 x 55mm)
Weight 4.6 lbs (2.1kg)
SAFETY
Safety Rating EN 61010-1, 600V Cat. III, Pollution Degree 2
Double Insulation Yes
CE Mark Yes

1Crest Factor at 6500A = 1

 

 

MicroDAQ.com accepts
Visa, MasterCard and American Express
Buy Data Loggers from Microdaq.com with Visa, MasterCard and American Express

All prices are in U.S. Dollars.
No U.S. sales tax