AC Exception Voltage Simple Logger®
AEMC AC Exception Logger for Electrical Sags and Swells
The AC Exception Voltage Simple Logger® Model L215 is designed for short-term sags and swells. The
logger samples the input 10 times per second and only stores
the data when an alarm threshold is crossed, thus maximizing
its use of memory. The 65,000-point storage capacity of the logger
provides enough memory to store more than 1000 events. The AC Exception Voltage datalogger is powered by the AC voltage signal it is monitoring
and incorporates a backup battery to provide up to one year of
additional operation and data storage protection.
The Keyspan USB 4-Port Serial Adapter is available for USB Connectivity.
Included with each Simple Logger®
>> Simple Logger Software
>> 9V Alkaline Battery
NOTE: Large Quantity Discounts Are Available!
Features Specifications
| Description |
Part Number |
Qty 1-9 |
Qty 10+ |
|
| AEMC Simple Logger RMS Voltage, 0 to 250VAC Input |
L215
|
$349.00 |
call |
 |
| Optional Acessories |
| 9 Volt Lithium battery, 1200 mAH |
U9VL-FP
|
$10.00 |
call |
 |
| USB Serial Adapter |
Cable-USB232
|
$39.00 |
$35.00 |
 |
| USB 4-Port Serial Adapter |
USA-49WG
|
$149.00 |
call |
 |
AC Exception Voltage Simple Logger® Features
- 10 Samples per Second
- Stores data when alarm level is tripped
- True RMS measurements
- 64K storage memory
- Detect sags and swells
- Scale automatically selected by software
- Software programmable HI and LO alarm levels
- Alarm trip LED indicator
AC Exception Voltage Simple Logger® Specifications
| Measurement Range |
0 to 250Vrms |
| Number of Channels |
1 |
| Input Connection |
Recessed Safety 4mm Banana Jacks |
| Resolution |
12 Bit, 250mV max |
| Accuracy |
1% of Reading + 250mV |
| Sample Rate |
36000/hr (10 samples/sec) |
| Storage Technique |
Exception recording
in FIFO mode; 60 samples stored
when alarm is tripped. Each 60 sample
recording is considered to be a packet.
When memory is full, data will be overwritten
one packet at a time beginning
with the oldest. Recording only occurs
during alarm conditions. |
| Data Storage |
65,536 readings |
| Power |
AC powered with 9V Alkaline
battery back-up |
| Battery Life |
Up to 1 year of recording @ 25°C |
| Output |
RS-232 via DB-9 connector
(@ 4800 baud) |
| Indicators |
Red LED double flashes
in LOGGING, single flashes in
STANDBY and is off in OFF mode.
Amber LED flashes once every
2 seconds when alarm level has been
tripped. Amber light can only be
reset by stopping the recording and
downloading the data. |
| Controls |
One button used to start and
stop recording sessions and to turn the
data logger on and off |
| Dimensions |
2 7/8" x 2 5/16" x 1 5/8"
(73 x 59 x 41mm) |
| Weight |
(with battery) 5 oz (140g) |
| Mounting |
Base plate mounting holes or Velcro® pads supplied loose |
| Operating Temperature |
-4 to +158°F (-20 to +70°C) |
| Storage Temperature |
-4 to +174°F (-20 to +80°C) |
| Relative Humidity |
5 to 95% non-condensing |
MicroDAQ.com accepts Visa, MasterCard and American Express

All prices are in U.S. Dollars.
No U.S. sales tax
|