Data Loggers - Your Source for Temperature Data Loggers, Humidity Data Loggers, Pressure Data Loggers,Relative Humidity Data Loggers,CO data loggers,CO2 data loggers,Rainfall Gauges,Soil Moisture Content Measurement and many other data logging,measurement or recording devices

Air Velocity Sensors

Onset Indoor Airflow & Gas Velocity Sensor with Range up to 10 Meters/Second

Air Velocity Sensor >> Measures Air & Inert Gas Velocity
>> Current Draw (12 Volt Excitation): 70 mA
>> Output: 0 to 4 Volts DC
>> Response Time: 1.5 seconds
>> Ability to Measure Air Velocity which CFM can be Calculated
>> Available in 1 or 2 Piece Versions

Compatible with
>> HOBO U30 Energy Monitor (with Analog Port Selection)
>> HOBO Energy Logger Pro (with Analog Module #S-FS-CVIA Required)

NOTE: 4 Week Lead Time Required!

  • Specifications
  • Documentation
  • Applications
  • Purchase

Air Velocity Sensor Specifications

Measurement Range T-DCI-F900-L-O: 0.15 to 5.0 m/s (30 to 985 fpm)
T-DCI-F900-L-P: 0.15 to 10.0 m/s (30 to 1969 fpm)
T-DCI-F900-S-P: 0.15 to 10.0 m/s (30 to 1969 fpm)
T-DCI-F900-S-O: 0.15 to 5.0 m/s (30 to 985 fpm)
Accuracy Greater of 10% of Reading or ±0.05 m/s or 1% Full Scale
Vibration up to 25 G
Acceptable Angle ±300 from Perpindicular
Repeatability ±1% Under Same Conditions
Standard Medium Air at Standard Pressure (101.3 kPa, 29.95" Hg)
Supply Voltage 7 to 13 Volts DC
Supply Current 40 to 75 mA (10K ohm Nominal)
Warm-Up Time < 5 Seconds
Response Time 1.5 Seconds
Output Calibrated Range: Linear 0 to 4 Volts DC Full Scale
Beyond Calibrated Range: Up to 4.9 Volts DC
Media Air, Various Liquids
Sensor Head Material Plastic
Operating Range Temperature: 0 to 70°C (32°F to 158°F)
Storage Range Temperature: -10°C to 100°C
Dimensions T-DCI-F900-L-O: 91mm x 12mm Diameter
T-DCI-F900-L-P: 91mm x 12mm Diameter
T-DCI-F900-S-P: 100mm x 12mm Diameter
T-DCI-F900-S-O: 100mm x 12mm Diameter
Weight T-DCI-F900-L-O: 1.8 oz.
T-DCI-F900-L-P: 1.8 oz.
T-DCI-F900-S-P: 1.0 oz
T-DCI-F900-S-O: 1.0 oz.

Air Velocity Sensor Documentation

Instructions on Connecting Air Velocity Sensor to H22 Energy Logger and U30 Energy Monitors. View PDF.

Air Velocity Sensor Applications

Airflow Measurement in HVAC Systems, Industrial Processes, Automotive, Air Filtration Systems, Electronic Enclosures and Critical Containment Areas.


Air Velocity Sensor w/ 0.15 to 10 m/s Range Air Velocity Sensor w/ 0.15 to 10 m/s Range
>> 1-Piece Sensor
>> Output: 0 to 4 Volts DC
>> Current Draw: 70 mA
>> Vibration: Up to 25G
Price: $235.00
Part #: T-DCI-F900-S-P

Air Velocity Sensor w/ 0.15 to 5.00 m/s Range Air Velocity Sensor w/ 0.15 to 5.00 m/s Range
>> 1-Piece Sensor
>> Output: 0 to 4 Volts DC
>> Current Draw: 70 mA
>> Vibration: Up to 25G
Price: $235.00
Part #: T-DCI-F900-S-O

Air Velocity Sensor w/ 0.15 to 10 m/s Range Air Velocity Sensor w/ 0.15 to 10 m/s Range
>> 2-Piece Sensor
>> Output: 0 to 4 Volts DC
>> Current Draw: 70 mA
>> Vibration: Up to 25G
Price: $319.00
Part #: T-DCI-F900-L-P

Air Velocity Sensor w/ 0.15 to 5.0 m/s Air Velocity Sensor w/ 0.15 to 5.0 m/s
>> 2-Piece Sensor
>> Output: 0 to 4 Volts DC
>> Current Draw: 70 mA
>> Vibration: Up to 25G
Price: $319.00
Part #: T-DCI-F900-L-O

 

MicroDAQ.com accepts
Visa, MasterCard and American Express
Buy Data Loggers from Microdaq.com with Visa, MasterCard and American Express

All prices are in U.S. Dollars.
No U.S. sales tax