PEL103 Power and Energy Data Logger w/ LCD Display

AEMC One, Two and three-Phase Power and Energy Data Loggers
SKU
2137.52
$2,370.25
  • Power (VA, W, var) & Energy (VAh, Wh, varh) Measurements on 50/60Hz, 400Hz and DC Systems
  • Measurement Range of 100mA to 10,000 Amps with MiniFlex Current Sensors (Included)
  • 4 Line LCD Display Shows 3 Phases Simultaneously on a Bright Blue Monochrome Backlit
  • Store Measured Current and Voltage Readings onto SD(HC) Cards up to 32 GB
  • RMS and DC Measurements of each Phase at 128 Samples per Cycle
  • Bluetooth, USB and Ethernet LAN Communications Options for Setup and Configuration
  • New! Android App to Connect, Configure, Setup, View Data Using Bluetooth or WiFi Communications

Includes Tool Bag, (3) MiniFlex Current Sensors, USB Cable, (4) Black Test Leads w/ Alligator Clips, AC Power Adapter, (12) Color-Coded ID Markers, Multifix Mounting System, Safety Card, 2 GB SD Card and USB-SD Card Reader, USB Memory Stick with User Manual and DataView PC Software

Special order - typical lead time is 2-4 weeks, however there may be shipping delays beyond our control

Overview of the AEMC PEL103 Power and Energy Data Logger

The AEMC PEL 103 power and energy data logger w/ LCD display is easy to use and cost-effective. It reads and records 1, 2 or 3-phase RMS voltage and current measurements. This three-phase power and energy data logger can be used by contractors, electricians and engineers engaged in system monitoring and upgrades. Data reports can be easily generated using the supplied standard reports which are fully customizable.

The slim design of the PEL 103 allows it and its current sensors to be mounted inside a panel while allowing the door to close in most cases. The logger measures and records three True RMS voltage and current inputs, Watts, VARS, VA, and Energy (kWh & kVA). The logger can use this data to calculate and record Power Factor (PF), Crest Factor, Displacement Power Factor (DPF), Frequency, and THD. Individual harmonic percent information, selectable from the 1 to the 50th harmonic, is also recorded.

AEMC 2137.52 PEL103 Power and Energy Data Logger Specifications

Input Channels (3) Current Inputs via Custom 4 pin Jacks
(3) Voltage Inputs via 4mm Safety Banana Jacks
Voltage
50/60 Hz: 42.5 Hz to 69 Hz @ ±0.1 Hz
400 Hz: 340 Hz to 460 Hz
DC: 100 to 1000 VDC @ ±1% Reading ± 3 Volts (0.1V Resolution)
50/60Hz Voltage
(Single-Phase RMS)
Measurement Range: 100 to 1000 rms
Accuracy: ±0.2% of Reading ±0.2 Volts
Resolution: 0.1 Volts
50/60Hz Voltage
(Phase to Phase RMS)
Measurement Range: 100 to 2000 Vrms
Accuracy: ±0.2% of Reading ±0.4 Volts
Resolution: 0.1 Volts to 1.0 Volt
400Hz Voltage
(Single-Phase RMS)
Measurement Range: 100 to 600 Vrms
Accuracy: ±1% of Reading ± 1 Volt
Resolution: 0.1 Volt
400Hz Voltage
(Phase to Phase RMS)
Measurement Range: 200 to 1200 Vrms
Accuracy: ±1% of Reading ±1 Volt
Resolution: 0.1 Volts to 1.0 Volt
DC Voltage
(PT Ratios)
Range: 50 Volts to 65,000 Volts (Programmable)
Resolution: 0.01 Volts to 0.1 Volts
Current Sensor Type: MiniFlex Sensor Probe (#MA-193)
100mA - 100Arms: ±1% ±50mA @ 1-100mA Resolution
20A - 400Arms: ±1% ±0.2A @ 10 to 100mA Resolution
100A - 2000Arms: ±1% ±1A @ 0.1 to 1A Resolution
500A - 10,000Arms: ±1% @ 0.1 to 1A Resolution
CT Ratios: Programmable 1:1 to 25,000:1 (Probe Dependent)
Active Power Measurement Range: -2 to 2GW
Accuracy: ±0.5% of Reading ±0.005% Pnom
Resolution: 0.001W
Reactive Power Measurement Range: -2 to 2Gvar
Accuracy: ±1% of Reading ±0.01% Qnom
Resolution: 0.001var
Apparent Power Measurement Range: 0 to 2GVA
Accuracy: ±0.5% of Reading ±0.005% Snom
Resolution: 0.001VA
Power Factor Measurement Range: -1 to 1
Accuracy: ±0.05
Resolution: 0.001
Tangent (active/reactive power ratio) Measurement Range: -3.2 to 3.2
Accuracy: ±0.02
Resolution: 0.001
Active Energy Measurement Range: 0 to 4 x 1018
Accuracy: ±0.5% of Reading
Resolution: 1Wh
Reactive Energy Measurement Range: 0 to 4 x 1018
Accuracy: ±2% of Reading
Resolution: 1varh
Apparent Energy Measurement Range: 0 to 4 x 1018
Accuracy: ±0.5% of Reading
Resolution: 1Vah
Total Harmonic Distortion (THD) ±655%
Individual Harmonics 1 to 50 Displayed in Percentage; 1 to 7 at 400Hz
Sampling Frequency 50/60 Hz: 128 Samples per Cycle
400 Hz: 16 Samples per cycle
Data Storage Rate 1 per Second
Demand Period Storage Rate 1, 2, 3, 4, 5, 6, 10, 12, 15, 20,30 and 60 Minutes (User Selectable)
Recorded Parameters V, I, W, VA, var, PF, Tan, Wh, Vah, varh, THD (V and I), Individual Harmonics (1 to 50 per Phase), Crest Factor (CF), Cos f / DPF
Event Log Tracks and Records Status Changes and Error Messages Along with Recorded Data
LED Indicators Bluetooth Active, Recording Status, Phase Connection Reversal, Overload, Battery Status, and SD Card Status
Data Storage Capacity 2GB SD Card (Included)
NOTE: SD Cards (up to 2 GB); SDHC Cards (4 to 32 GB) Formatted FAT32 are Supported
Communication Ports USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1
NOTE: Class II Bluetooth Range is Restricted to 40 ft.
Computers without Bluetooth will require a Bluetooth Radio Adapter
Display Type: 4 Line Monochrome Backlit LCD w/ Adjustable Brightness and Contrast
Dimensions: 67mm x 55mm (2.63" x 2.16")
NOTE: Display Available with PEL103 Version Only
Power Source Rechargeable 8.4 Volt NiMH Battery Pack
(5 Hour Charge Time)
Battery Life
NOTE: Battery Life Depends on Measurement Environment, Recording Interval and Battery Performance
Case Double Insulated, Rubber Over Molded, Polycarbonate
UL94 V1 Rated / IP54 (Non Operating)
Mounting Embedded Magnets on Back Side, Keyhole Slot on Back Side
Security Kensington Anti-theft System
Software DataView Software (Included)
OS Compatibility Windows 11, 10 and 7 (32 and 64 Bit)
Operating Environment Temperature: 0°C to 50°C (32°F to 122°F)
Humidity: 0 to 85% RH
Standards Compliance IEC 61010-1:Ed3 IEC61010-2-030:Ed1 for 1000 Volt CAT III / 600 Volt CAT IV; Polution Degree 2; CE
Weight <1 kg
Dimensions 256mm x 125mm x 37mm (10.08" x 4.92" x 1.46")
Customer Questions
Is the software compatible with Windows 10?
Yes, it will work with Windows10
Please, mind that only logged in users can submit questions