Onset HOBO EG4130 30-Input Meter Data Logger

  • Onset HOBO EG4130 30-Input Meter Data Logger
  • Onset HOBO EG4130 30-Input Meter Data Logger
  • Onset HOBO EG4130 30-Input Meter Data Logger


Onset EG4130 Pro 30 Input Meter Data Logger

Part Number: EG4130

Ask a question (1)

Be the first to review this product


  • 30 Channel Energy Meter with 0.5% Revenue Grade Accuracy Compliance

  • Ability to Measure Residential or Commercial Circuit Panels, up to 3-Phase 277/480 Volts AC and 6900 Amps

  • HomePlug AV Powerline Communication, Ethernet Port and (2) USB Ports for Additional Options

  • Embedded Web Server Connects the Meter to the Internet or LAN

  • Supports Large Number of Current Transformers (CTs) to Accommodate Most Loads


Supports AC Current, AC Voltage, Amps, Kilowatt Hours, Kilowatts, Volt-Amp Reactive, Volt-Amp Reactive Hour, Watt Hours and Watts

Special order - please allow 3-5 business days for this item to ship.

$850.00

Onset EG4130 Pro 30 Input Meter and Data Logger Specifications

Data Channels 30 Input Channels
AC Voltage L1: 85 to 277 Vrms
L2: 0 to 277 Vrms
L3: 0 to 277 Vrms
DC Voltage 42 Vrms
Power: 9 to 60 Volts DC
Measurement: ± 60 Volts DC
Current Number of Channels: 30
5 to 6900 Amps Max per Channel
Fully Isolated Inputs
Frequency 50 or 60 Hz
Logging Values V, A, W, Wh, Hz, VA, VAr, THD, deg
Power Draw 12 Watt Max, 2 Watt Typical
Operating Range Temperature: -30°C to 70°C (-22°F to 158°F)
Humidity: 80% up to 31°C
Max Altitude 4000 Meters (13,123 ft)
Measurement Category Overvoltage Category III
Location Open Type Indoor Device
Pollution Degree 2
Register Count 64 (Data Storage Points)
Granularity (Duration/avg) 1 Hour/1 Second
1 Year/1 Minute
10 Years/15 Minute
Device Lifetime/1 Day
Safety IEC/UL 61010-1 Ed. 3.0 B:2010
CE IEC 61000-6-1 Ed. 3.0 B:2016
IEC 61000-6-3 Ed. 2.1 B:2011
FCC FCC Title 47 CFR Part 15-Subpart B Class B
ICES-003 Information Technology Equipment Class B
Power Source AA 1.5 Volt Lithium Battery (User-Replaceable)
Communications Homeplug AV: Compatible with Homeplug AV-Adapter within approximately 1000 ft. on Same Phase as L1
Ethernet: IEEE 802.3 - LAN
Compatible Browsers Google Chrome, Firefox, Safari, Internet Explorer
Material Enclosure FRABS
Weight 300 grams (0.66 lbs)
Dimensions 17.0 cm x 8.0 cm x 4.6 cm (6.7" x 3.15" x 1.81")

Customer Reviews

Write Your Own Review

You're reviewing: Onset EG4130 Pro 30 Input Meter Data Logger

How do you rate this product? *

  1 star 2 stars 3 stars 4 stars 5 stars
Price
Quality
Value
  • Answer:

    The logger will store the latest hour of data second by second and is stored in the volatile memory (cleared upon reboot).  The latest year of data is stored in minute-by-minute granularity.  The following 10 years of data is stored in 15 minute granularity.  After that, data is condensed to 1-day for the lifetime of the device.   